EXPANSION of TWO EXISTING SUBSTATIONS in JEFFERSON and PLAQUEMINES PARISH
NAME OF APPLICANT: Entergy Louisiana, LLC, ATTN: Morris P. Hebert, Inc., Mr. Timothy Robertson, at 10343 Siegen Lane, Building 4-B, Baton Rouge, Louisiana 70810.
LOCATION OF WORK: Barataria Substation located on Louisiana Highway 301 in Lafitte, Louisiana, in Jefferson Parish and Alliance Substation located on Louisiana Highway 23, in Alliance, Louisiana, in Plaquemines Parish, Louisiana as shown on the attached drawings.
HUC: 08090301; East – Central Louisiana Coastal
CHARACTER OF WORK: To expand two existing substation locations. The addition to the Barataria substation will consist of a 1.56 acre expansion area and the installation of one three-pole electrical structure adjacent to the facility. The addition to the Alliance substation will consist of a 3.54 acre expansion area. Additionally, Entergy is proposing to install approximately 0.60 miles of transmission lines from the expansion area to a customer substation. The new transmission lines will run adjacent to an existing transmission ROW and will consist of 18 new electrical pole installations. This project would require permanent impacts totaling 1.94 acres of bottomland hardwood wetlands and a conversion of 0.46 acres of bottomland hardwood wetlands to herbaceous wetlands. The applicant proposes to purchase credits from a mitigation bank to offset any unavoidable losses to wetland functions caused by project implementation.
JOINT PUBLIC NOTICE
14 May 2018
United States Army
Corps of Engineers
New Orleans District
Regulatory Branch
7400 Leake Avenue
New Orleans, Louisiana 70118
State of Louisiana
Department of Environmental Quality
ATTN: Water Quality Certifications
Post Office Box 4313
Baton Rouge, Louisiana 70821-4313
(504) 862-2279
kara.vick@usace.army.mil
Project Manager
Kara Vick
Permit Application Number
MVN 2018-00218-EV
(225) 219-3225
Project Manager
Elizabeth Hill
WQC Application Number
WQC 180508-01
Interested parties are hereby notified that a permit application has been received by the New
Orleans District of the U.S. Army Corps of Engineers pursuant to: [X] Section 10 of the Rivers and
Harbors Act of March 3, 1899 (30 Stat. 1151; 33 USC 403); and/or [X] Section 404 of the Clean
Water Act (86 Stat. 816; 33 USC 1344).
Application has also been made to the Louisiana Department of Environmental Quality for a
Water Quality Certification (WQC) in accordance with statutory authority contained in LRS30:2047
A(3), and provisions of Section 401 of the Clean Water Act (P.L.95-17).
EXPANSION of TWO EXISTING SUBSTATIONS in JEFFERSON and PLAQUEMINES PARISH
NAME OF APPLICANT: Entergy Louisiana, LLC, ATTN: Morris P. Hebert, Inc.,
Mr. Timothy Robertson, at 10343 Siegen Lane, Building 4-B, Baton Rouge, Louisiana 70810.
LOCATION OF WORK: Barataria Substation located on Louisiana Highway 301 in Lafitte, Louisiana,
in Jefferson Parish and Alliance Substation located on Louisiana Highway 23, in Alliance, Louisiana,
in Plaquemines Parish, Louisiana as shown on the attached drawings.
HUC: 08090301; East Central Louisiana Coastal
CHARACTER OF WORK: To expand two existing substation locations. The addition to the
Barataria substation will consist of a 1.56 acre expansion area and the installation of one three-pole
electrical structure adjacent to the facility. The addition to the Alliance substation will consist of a 3.54
acre expansion area. Additionally, Entergy is proposing to install approximately 0.60 miles of
transmission lines from the expansion area to a customer substation. The new transmission lines will
run adjacent to an existing transmission ROW and will consist of 18 new electrical pole installations.
This project would require permanent impacts totaling 1.94 acres of bottomland hardwood wetlands
and a conversion of 0.46 acres of bottomland hardwood wetlands to herbaceous wetlands. The
applicant proposes to purchase credits from a mitigation bank to offset any unavoidable losses to
wetland functions caused by project implementation.
-2The comment period for the Department of the Army Permit and the Louisiana Department of
Environmental Quality WQC will close 20 days from the date of this joint public notice. Written
comments, including suggestions for modifications or objections to the proposed work, stating
reasons thereof, are being solicited from anyone having interest in this permit and/or this WQC
request and must be mailed so as to be received before or by the last day of the comment period.
Letters concerning the Corps of Engineers permit application must reference the applicant's name
and the Permit Application Number, and be mailed to the Corps of Engineers at the address above,
ATTENTION: REGULATORY BRANCH. Similar letters concerning the Water Quality Certification
must reference the applicant's name and the WQC Application number and be mailed to the
Louisiana Department of Environmental Quality at the address above. Individuals or parties may
request an extension of time in which to comment on the proposed work by writing or
e-mailing the Corps of Engineers Project Manager listed above. Any request must be specific and
substantively supportive of the requested extension, and received by this office prior to the end of the
initial comment period. The Section Chief will review the request and the requestor will be promptly
notified of the decision to grant or deny the request. If granted, the time extension will be continuous
to the initial comment period and, inclusive of the initial comment period, will not exceed a total of 30
calendar days.
The application for this proposed project is on file with the Louisiana Department of
Environmental Quality and may be examined during weekdays between 8:00 a.m. and 4:30 p.m.
Copies may be obtained upon payment of costs of reproduction.
Corps of Engineers Permit Criteria
The decision whether to issue a permit will be based on an evaluation of the probable impacts,
including cumulative impacts of the proposed activity on the public interest. That decision will reflect
the national concern for both protection and utilization of important resources. The benefit which
reasonably may be expected to accrue from the proposal must be balanced against its reasonably
foreseeable detriments. All factors which may be relevant to the proposal will be considered including
the cumulative effects thereof; among those are conservation, economics, aesthetics, general
environmental concerns, wetlands, historic properties, fish and wildlife values, flood hazards,
floodplain values, land use, navigation, shoreline erosion and accretion, recreation, water supply and
conservation, water quality, energy needs, safety, food and fiber production, mineral needs,
considerations of property ownership and, in general, the needs and welfare of the people.
The U.S. Army Corps of Engineers is soliciting comments from the public, federal, state, and
local agencies and officials, Indian Tribes, and other interested parties in order to consider and
evaluate the impacts of this proposed activity. Any comments received will be considered by the U.S.
Army Corps of Engineers to determine whether to make, modify, condition, or deny a permit for this
proposal. To make this decision, comments are used to assess impacts on endangered species,
historic properties, water quality, general environmental effects, and other public interest factors listed
above. Comments are used in the preparation of an Environmental Assessment and/or an
Environmental Impact Statement pursuant to the National Environmental Policy Act. Comments are
also used to determine the need for a public hearing and to determine the overall public interest of the
proposed activity.
The New Orleans District is unaware of properties listed on the National Register of Historic
Places near the proposed work. The possibility exists that the proposed work may damage or
destroy presently unknown archeological, scientific, prehistorical, historical sites, or data. Issuance of
this public notice solicits input from the State Archeologist and State Historic Preservation Officer
regarding potential impacts to cultural resources.
Our initial finding is that the proposed work would neither affect any species listed as
endangered, nor habitat designated as critical to the survival and recovery of species listed as
-3endangered by the U.S. Department of Commerce.
Utilizing Standard Local Operating Procedure for Endangered Species in Louisiana (SLOPES),
dated October 22, 2014, between the U.S. Army Corps of Engineers, New Orleans and U.S. Fish and
Wildlife Service, Ecological Services Office, the Corps has determined that the proposed activity
would have no effect on any listed species nor affect any habitat designated as critical to the survival
and recovery of any endangered species of concern to the USFW.
This notice initiates the Essential Fish Habitat (EFH) consultation requirements of the
Magnuson-Stevens Fishery Conservation and Management Act. The applicant's proposal would
result in the destruction or alteration of 0.06 acre of EFH utilized by various life stages of red drum
and penaeid shrimp. Our initial determination is that the proposed action would not have a
substantial adverse impact on EFH or federally managed fisheries in the Gulf of Mexico. Our final
determination relative to project impacts and the need for mitigation measures is subject to review by
and coordination with the National Marine Fisheries Service.
If the proposed work involves deposits of dredged or fill material into navigable waters, the
evaluation of the probable impacts will include the application of guidelines established by the
Administrator of the Environmental Protection Agency. Also, a certification that the proposed activity
will not violate applicable water quality standards will be required from the Department of
Environmental Quality before a permit is issued.
Any person may request, in writing, within the comment period specified in this notice, that a
public hearing be held to consider this application. Requests for public hearings shall state, with
particularity, the reasons for holding a public hearing.
The applicant has certified that the proposed activity described in the application complies with
and will be conducted in a manner that is consistent with the Louisiana Coastal Resources Program.
The Department of the Army permit will not be issued unless the applicant received approval or a
waiver of the Coastal Use Permit by the Department of Natural Resources.
You are requested to communicate the information contained in this notice to any other parties
whom you deem likely to have interest in the matter.
Michael V. Farabee
Chief, Eastern Evaluation Section
Enclosure
Ü
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
SECTIONS 5, 15-T15S, 16S-R23E, R25E
BARATARIA SUBSTATION
JEFFERSON PARISH
LAT: 29°45' 36.02"N
LON: 90°7' 42.83"W
NEW ORLEANS
ALLIANCE SUBSTATION
PLAQUEMINES PARISH
LAT: 29°40' 31.94"N
LON: 89°58' 52.24"W
"
/
LAFITTE
"
/
PORT SULPHUR
¹
_
^
/
"
FILE LOCATION: G:\ENTERGY\12900\MAPS\12900_VICINITY.MXD
12
"
/
6
0
12 Miles
Construction Area
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
0
/
"
20 40 Miles
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
VICINITY MAP
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 1
SCALE: 1 IN = 12 MI
DATE: 2/20/2018
JOB NO.: 12900-00
GIS FILE: 12900_VICINITY.MXD
Ü
PLAQUEMINES PARISH, LOUISIANA
29° 58' 50.485"N
89° 40' 33.623"W
SECTION 5-T16S-R25E
29° 40' 31.975"N
89° 58' 55.534"W
PROPOSED ALLIANCE
SUBSTATION EXPANSION
(± 3.54 ACRES)
29° 40' 30.258"N
89° 58' 40.146"W
HIG
3
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_CONST_.MXD
2
AY
HW
EXISTING ALLIANCE SUBSTATION
29° 40' 28.302"N
89° 58' 54.212"W
0
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
75
150
300
Feet
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CONSTRUCTION AREA MAP
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 2
SCALE: 1 IN = 150 FT
DATE: 1/23/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_CONST_.MXD
Ü
PLAQUEMINES PARISH, LOUISIANA
CUSTOMER
SUBSTATION
127
PROPOSED ROW
175' W x 3,100' L
&&
-
128
1
2
&
&
125
&&
-
3
4
23
&&
-
HIGHWAY
129
SECTION 5-T16S-R25E
130
5
&&
-
131
132
NOTE: SUBSTATION EXPANSION
CONSTRUCTION AREA WILL BE
CLEARED AND GRUBBED. 18" OF
NATIVE SOIL WILL BE REMOVED.
ENTIRE CONSTRUCTION AREA WILL
BE BACKFILLED WITH SAND AND
LIMESTONE OVER GEOTEXTILE
FABRIC, EXCLUDING THE PROPOSED
LEVEE AREA.
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_PLAN.MXD
&
7
&&
-
133
&&
-6
8
&&
-
134
&
&
PROPOSED ALLIANCE
SUBSTATION EXPANSION
(± 3.54 ACRES)
9
EXISTING ALLIANCE
SUBSTATION
PROPOSED POLE LOCATION
EXISTING ROW
PROPOSED ROW
OTHER WATERS
PROPOSED FILL AREA (± 3.54 ACRES)
WETLANDS TO BE IMPACTED
FORESTED WETLANDS
0
HERBACEOUS WETLANDS
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
250
500
1,000
Feet
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
PLAN VIEW MAP
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 3
SCALE: 1 IN = 500 FT
DATE: 3/13/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_PLAN.MXD
Ü
PLAQUEMINES PARISH, LOUISIANA
SECTION 5-T16S-R25E
"A"
PROPOSED 20' LIMESTONE
DRIVEWAYS
O
PR
PROPOSED ELECTRICAL STRUCTURES
(26 STRUCTURES TOTAL)
E
NC
' FE
4
ED
EE
OS
EV
OP
R
DL
P
E
OS
OP
PR
D6
SE
PO
NC
' FE
E
PR
PROPOSED DRAINAGE
SWALE
ED
OS
OP
E
EE
PROPOSED ROW
EXISTING ALLIANCE SUBSTATION
NC
V
LE
EXISTING ROW
E
6' F
ING
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_SITE_PLAN.MXD
ING
IST
EX
IST
EX
NOTE: SUBSTATION EXPANSION
CONSTRUCTION AREA WILL BE
CLEARED AND GRUBBED. 18" OF
NATIVE SOIL WILL BE REMOVED.
ENTIRE CONSTRUCTION AREA WILL
BE BACKFILLED WITH SAND AND
LIMESTONE OVER GEOTEXTILE
FABRIC, EXCLUDING THE PROPOSED
LEVEE AREA.
3
CE
FEN ED)
G
IN MOV
IST
E
EX BE R
O
T
(
EE
EV
)
G L OVED
N
I
T EM
S
I
EX BE R
(TO
2
AY
HW
E
"A"
HIG
C
EN
6' F
PROPOSED HEADWALLS
AND CULVERT
(SEE SHEET 6 FOR
TYPICAL)
PROPOSED FILL AREA (± 3.54 ACRES)
WETLANDS TO BE IMPACTED
FORESTED WETLANDS
0
HERBACEOUS WETLANDS
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
50
100
200
Feet
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
DETAILED PLAN VIEW MAP
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 4
SCALE: 1 IN = 100 FT
DATE: 1/31/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_SITE_PLAN.MXD
CROSS-SECTION "A" - "A" (ALLIANCE SUBSTATION)
NOT TO SCALE
Proposed Electrical Structure
to be constructed after removal
of existing levee
Proposed Electrical Structures
(26 Structures Total)
±25'
±25'
±25'
±25'
Proposed 6' Chain-link
Fence with Barb Wire
Proposed 4'
Perimeter Fence
±15'
X
X
X
X
±30'
X
Existing Fence
(To Be Removed)
Proposed 18" Sand
Proposed Foundation Piles
(12" X 40' - 360 Total)
Proposed 12" #610 Grey
(12" X 60' - 653 Total)
Limestone over Geotextile Fabric
(12" X 75' - 422 Total)
Proposed Drainage
Headwall with 30" Culvert
Proposed Levee
(±800 x ±30' x ±5')
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_CROSS.MXD
±75'
±30'
Proposed Drainage Swale
(6" #4 Ballast over
Geotextile Fabric)
X
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
370'
Existing Substation
Boundary
Existing Levee
(To Be Removed)
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CROSS-SECTION
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY: RM
REVISION BY:
SHEET: 5
SCALE: NOT TO SCALE
DATE: 3/6/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_CROSS.MXD
TYPICAL DRAINAGE HEADWALL AND CULVERT
NOT TO SCALE
50"
10"
36"
102"
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_TYPICAL.MXD
30"
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
TYPICAL
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 6
SCALE: NOT TO SCALE
DATE: 3/6/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_TYPICAL.MXD
TYPICAL ELECTRICAL POLE
NOT TO SCALE
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_TYPICAL_POLE.MXD
PROPOSED STEEL
ELECTRICAL POLE
(18 TOTAL)
4.5'- 6'
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
T-LINE STRUCTURES
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
TYPICAL
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 7
SCALE: NOT TO SCALE
DATE: 1/31/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_TYPICAL_POLE.MXD
ALLIANCE SUBSTATION - CALCULATION SHEET
EXCAVATION/FILL CHART
& EQUIPMENT LIST FOR PROPOSED
SUBSTATION EXPANSION
EXCAVATIONS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
0
HERBACEOUS WETLANDS:
225.87
FORESTED WETLANDS:
1,048.67
NON-WET AREAS
4,259.20
FILL AREAS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
0
HERBACEOUS WETLANDS:
564.67
FORESTED WETLANDS:
4517.30
NON-WET AREAS
10,648
FILL MATERIALS:
CLASSIFICATION
CUBIC YARDS
CONCRETE:
0
CRUSHED STONE OR GRAVEL:
6,292
NATIVE MATERIAL (CLAY, MUD, SOIL):
2,222 (levee)
CONCRETE MATTING:
0
SAND:
9,438
ADDITIONAL IMPACTS (ROW CONVERSION):
CLASSIFICATION
ACREAGE
FORESTED WETLANDS:
0.46
EQUIPMENT LIST:
CRANES
TRACTORS
WIRE PULLING EQUIPMENT
SKIDDERS
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_CALC_SUB_.MXD
BUCKET AND AERIAL PLATFORMS TRUCKS
ACREAGE
0
0.14
0.24
3.16
ACREAGE
0
0.14
0.24
3.16
TANKER TRUCKS
VIBRATORY HAMMER AND HYDRAULIC POWER UNIT
TRAILERS
BULLDOZERS
SLEDS
EXCAVATORS, TRACKHOES, AND BACKHOES
VEGETATION CLEARING EQUIPMENT
DIGGER DERRICKS AND DRILL RIGS
VEGETATION INCINERATOR
GRADERS
HELICOPTERS
FORKLIFTS
MARSH BUGGIES
LOADERS
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THESE DRAWINGS
ARE TO BE USED EXCLUSIVELY
FOR THE ACQUISITION OF
REGULATORY PERMITS
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CALCULATION SHEET
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 8
SCALE: NOT TO SCALE
DATE: 1/31/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_CALC_SUB_.MXD
T-LINE STRUCTURES - CALCULATION SHEET
EXCAVATION/FILL CHART
& EQUIPMENT LIST FOR PROPOSED
ELECTRIC POLE INSTALLATION
EXCAVATIONS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
0
HERBACEOUS WETLANDS:
0
FORESTED WETLANDS:
0
NON-WET AREAS
0
FILL AREAS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
0
HERBACEOUS WETLANDS:
0
FORESTED WETLANDS:
0
NON-WET AREAS
0
FILL MATERIALS:
CLASSIFICATION
CUBIC YARDS
CONCRETE:
0
CRUSHED STONE OR GRAVEL:
0
NATIVE MATERIAL (CLAY, MUD, SOIL):
0
CONCRETE MATTING:
0
SAND:
0
ADDITIONAL IMPACTS (POLE INSTALLATION):
CLASSIFICATION
ACREAGE
OTHER WATERS
0.0104
FORESTED WETLANDS:
0
EQUIPMENT LIST:
CRANES
TRACTORS
WIRE PULLING EQUIPMENT
SKIDDERS
FILE LOCATION: G:\ENTERGY\12900\MAPS\ALLIANCE\12900_ALLIANCE_CALC_POLE_.MXD
BUCKET AND AERIAL PLATFORMS TRUCKS
ACREAGE
0
0
0
0
ACREAGE
0
0
0
0
TANKER TRUCKS
VIBRATORY HAMMER AND HYDRAULIC POWER UNIT
TRAILERS
BULLDOZERS
SLEDS
EXCAVATORS, TRACKHOES, AND BACKHOES
VEGETATION CLEARING EQUIPMENT
DIGGER DERRICKS AND DRILL RIGS
VEGETATION INCINERATOR
GRADERS
HELICOPTERS
FORKLIFTS
MARSH BUGGIES
LOADERS
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THESE DRAWINGS
ARE TO BE USED EXCLUSIVELY
FOR THE ACQUISITION OF
REGULATORY PERMITS
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
T-LINE STRUCTURES
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CALCULATION SHEET
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 9
SCALE: NOT TO SCALE
DATE: 1/31/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_CALC_POLE_.MXD
JEFFERSON PARISH, LOUISIANA
Ü
SECTION 10-T15S-R23E
29° 45' 38.292"N
90° 7' 43.159"W
PROPOSED BARATARIA
SUBSTATION EXPANSION
(± 1.56 ACRES)
29° 45' 35.496"N
90° 7' 46.699"W
29° 45' 34.805"N
89° 7' 40.400"W
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_CONST.MXD
EXISTING BARATARIA SUBSTATION
G
HI
AY
HW
1
30
29° 45' 32.906"N
90° 7' 44.649"W
0
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
50
100
200
Feet
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CONSTRUCTION AREA MAP
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 10
SCALE: 1 IN = 100 FT
DATE: 1/23/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_CONST.MXD
JEFFERSON PARISH, LOUISIANA
Ü
SECTION 10-T15S-R23E
PR
OP
'
25
±1
OS
ED
RO
PROPOSED ELECTRICAL
STRUCTURES
(9 STRUCTURES TOTAL)
W
W
NG
TI
IS
EX
RO
W
L
AL )
W AL
LE IC
PI P
E
T TY
NC
E E OR
FE
SH F
4
6'
D
ED 1
T
SE
OS EE
PO
OP S H
O
PR EE
PR
(S
RO
W
ED
RO
OS
G
OP
IN
IST
EX
PR
"A
"
&
&1A
&
/
"
/"
"
/
/
/"
"
/"
0'
PR
OP
6
E
EXISTING FENCE
(TO BE REMOVED)
HIG
"
"B
"A
"
D
E
OS
C
EN
'F
"
"B
9
±1
'
15
±2
EXISTING BARATARIA SUBSTATION
T
IS
EX
G
IN
N
FE
6'
ST
XI
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_PLAN.MXD
CE
E
"
/
&
EXISTING POLE LOCATION
IN
CE
AY
EN
F
EW
6'
V
RI
G
I
EX
PROPOSED POLE LOCATION
EXISTING ROW
PR
PROPOSED ROW (± 650' L)
S
O
NG
TI
D
ED
S
PO
D
Y
WA
VE
I
R
W
G
IN
EN
ID
PROPOSED FILL AREA (± 1.56 ACRES)
WETLANDS TO BE IMPACTED
HERBACEOUS WETLANDS
0
SCRUB SHRUB
OTHER WATERS
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
301
AY
W
H
NOTE: SUBSTATION EXPANSION
CONSTRUCTION AREA WILL BE
CLEARED AND GRUBBED. 36" OF
NATIVE SOIL WILL BE REMOVED.
ENTIRE CONSTRUCTION AREA WILL
BE BACKFILLED WITH SAND, AND
LIMESTONE OVER GEOTEXTILE
FABRIC.
75
150
300
Feet
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
DETAILED PLAN VIEW MAP
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 11
SCALE: 1 IN = 100 FT
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_PLAN.MXD
CROSS-SECTION "A" - "A" (BARATARIA SUBSTATION)
NOT TO SCALE
Existing Electrical Structures
(2 Structures Total)
Proposed Electrical Structures
(1 Structure Total)
±25'
±25'
Proposed ROW Boundary
±25'
±125'
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_CROSS.MXD
Existing ROW Boundary
NOTE: MEASURED DISTANCES ARE APPROXIMATED
FOR PERMITTING PURPOSES AND ARE NOT A
TRUE MEASURED DISTANCE.
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
±220'
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CROSS-SECTION
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 12
SCALE: NOT TO SCALE
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_CROSS.MXD
CROSS-SECTION "B" - "B" (BARATARIA SUBSTATION)
NOT TO SCALE
Proposed Electrical Structures
(9 Structures Total)
±25'
±25'
Proposed Sheet Pile Wall
(See Sheet 14 for Typical)
Existing Fence
(To Be Removed)
Proposed 6'
Chain-link Fence
X
X
±35'
±20'
±35'
X
X
Existing Substation
Boundary
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_CROSS_B.MXD
185'
Proposed 12" #610 Grey
Limestone over Geotextile Fabric
Foundation Piles
(12" X 50' - 531 Total)
Proposed 36" Sand
NOTE: MEASURED DISTANCES ARE APPROXIMATED
FOR PERMITTING PURPOSES AND ARE NOT A
TRUE MEASURED DISTANCE.
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CROSS-SECTION "B"
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 13
SCALE: NOT TO SCALE
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_CROSS_B.MXD
TYPICAL SHEET PILE WALL
NOT TO SCALE
INSIDE SUBSTATION
PROPERTY LINE
FENCE-SEE CIVIL
CENTER SHEET PILE BETWEEN
FENCE AND PROP. LINE TYP.
1' TO 1.5'
SEE CIVIL
SEE CIVIL FOR GRADES, SLOPE
AND FILL REQUIREMENTS
OUTSIDE SUBSTATION
EX. GRADE VARIES
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_TYPICAL.MXD
16'0"-PZ22 SHEET PILE WALL
SCALE: N.T.S.
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
TYPICAL
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 14
SCALE: NOT TO SCALE
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_TYPICAL.MXD
TYPICAL ELECTRICAL POLE
NOT TO SCALE
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_TYPICAL_POLE.MXD
PROPOSED STEEL
ELECTRICAL POLE
(1 TOTAL)
4.5'- 6'
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
T-LINE STRUCTURES
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
TYPICAL
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 15
SCALE: NOT TO SCALE
DATE: 1/31/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_TYPICAL_POLE.MXD
BARATARIA SUBSTATION - CALCULATION SHEET
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_CALC_SUB_.MXD
EXCAVATION/FILL CHART
& EQUIPMENT LIST FOR PROPOSED
SUBSTATION EXPANSION
EXCAVATIONS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
242
HERBACEOUS WETLANDS:
5,904.80
SCRUB SHRUB WETLANDS:
1,403.60
NON-WET AREAS
0
FILL AREAS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
322.67
HERBACEOUS WETLANDS:
7873.07
SCRUB SHRUB WETLANDS:
1871.47
NON-WET AREAS
0
FILL MATERIALS:
CLASSIFICATION
CUBIC YARDS
CONCRETE:
0
CRUSHED STONE OR GRAVEL:
2516.81
NATIVE MATERIAL (CLAY, MUD, SOIL):
0
CONCRETE MATTING:
0
SAND:
7550.4
ADDITIONAL IMPACTS (ROW CONVERSION)
CLASSIFICATION
ACREAGE
HERBACEOUS WETLANDS:
0
FORESTED WETLANDS:
0
CANAL CROSSING AREAS:
0
EQUIPMENT LIST:
CRANES
TRACTORS
WIRE PULLING EQUIPMENT
SKIDDERS
BUCKET AND AERIAL PLATFORMS TRUCKS
ACREAGE
0.05
1.22
0.29
0
ACREAGE
0.05
1.22
0.29
0
TANKER TRUCKS
VIBRATORY HAMMER AND HYDRAULIC POWER UNIT
BULLDOZERS
EXCAVATORS, TRACKHOES, AND BACKHOES
TRAILERS
SLEDS
VEGETATION CLEARING EQUIPMENT
DIGGER DERRICKS AND DRILL RIGS
VEGETATION INCINERATOR
GRADERS
HELICOPTERS
FORKLIFTS
MARSH BUGGIES
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THESE DRAWINGS
ARE TO BE USED EXCLUSIVELY
FOR THE ACQUISITION OF
REGULATORY PERMITS
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CALCULATION SHEET
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 16
SCALE: NOT TO SCALE
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_CALC_SUB_.MXD
FILE LOCATION: G:\ENTERGY\12900\MAPS\BARATARIA\12900_BARATARIA_CALC_ POLE_.MXD
T-LINE STRUCTURES - CALCULATION SHEET
EXCAVATION/FILL CHART
& EQUIPMENT LIST FOR PROPOSED
ELECTRIC POLE INSTALLATION EXPANSION
EXCAVATIONS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
0
HERBACEOUS WETLANDS:
0
SCRUB SHRUB WETLANDS:
0
NON-WET AREAS
0
FILL AREAS:
CLASSIFICATION
CUBIC YARDS
WATERBOTTOMS:
0
HERBACEOUS WETLANDS:
0
SCRUB SHRUB WETLANDS:
0
NON-WET AREAS
0
FILL MATERIALS:
CLASSIFICATION
CUBIC YARDS
CONCRETE:
0
CRUSHED STONE OR GRAVEL:
0
NATIVE MATERIAL (CLAY, MUD, SOIL):
0
CONCRETE MATTING:
0
SAND:
0
ADDITIONAL IMPACTS (POLE INSTALLATION)
CLASSIFICATION
ACREAGE
HERBACEOUS WETLANDS:
0.0078
FORESTED WETLANDS:
0
CANAL CROSSING AREAS:
0
EQUIPMENT LIST:
CRANES
TRACTORS
WIRE PULLING EQUIPMENT
SKIDDERS
BUCKET AND AERIAL PLATFORMS TRUCKS
ACREAGE
0
0
0
0
ACREAGE
0
0
0
0
TANKER TRUCKS
VIBRATORY HAMMER AND HYDRAULIC POWER UNIT
TRAILERS
BULLDOZERS
SLEDS
EXCAVATORS, TRACKHOES, AND BACKHOES
VEGETATION CLEARING EQUIPMENT
DIGGER DERRICKS AND DRILL RIGS
VEGETATION INCINERATOR
GRADERS
HELICOPTERS
FORKLIFTS
MARSH BUGGIES
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THESE DRAWINGS
ARE TO BE USED EXCLUSIVELY
FOR THE ACQUISITION OF
REGULATORY PERMITS
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
T-LINE STRUCTURES
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CALCULATION SHEET
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 17
SCALE: NOT TO SCALE
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_BARATARIA_CALC_ POLE_.MXD
FILE LOCATION: G:\ENTERGY\12900\MAPS\12900_ALLIANCE_BARATARIA_XY_.MXD
PROPOSED POLE LOCATION COORDINATES
BARATARIA SUBSTATION
NAME LAT
LON
X
1A
3662823.738 460415.1204 90° 7' 45.85" W
3662833.498 460435.8708 90° 7' 45.74" W
3662811.513 460395.783 90° 7' 45.99" W
Y
29° 45' 37.91" N
29° 45' 38.12" N
29° 45' 37.72" N
ALLIANCE SUBSTATION
NAME LAT
LON
X
125
3710250.885 432165.2598 89° 58' 51.56" W
1
3710243.94 432215.607 89° 58' 51.63" W
2
3709979.357 432201.0237 89° 58' 54.63" W
127
3709927.273 432214.2181 89° 58' 55.22" W
128
3709938.905 431792.2563 89° 58' 55.15" W
3
3709989.687 431786.1799 89° 58' 54.57" W
129
3709966.249 431199.3744 89° 58' 54.92" W
4
3710017.464 431202.4126 89° 58' 54.33" W
5
3710061.301 430880.364 89° 58' 53.88" W
130
3710007.482 430904.2355 89° 58' 54.49" W
6
3709863.385 430715.4334 89° 58' 56.15" W
131
3709832.569 430757.1001 89° 58' 56.49" W
7
3709699.322 430563.0897 89° 58' 58.03" W
132
3709649.409 430589.9994 89° 58' 58.59" W
8
3709723.628 430204.1487 89° 58' 57.80" W
133
3709673.714 430196.3362 89° 58' 58.37" W
9
3709840.381 429932.4473 89° 58' 56.51" W
134
3709812.169 429848.6799 89° 58' 56.84" W
Y
29° 40' 53.03" N
29° 40' 53.53" N
29° 40' 53.42" N
29° 40' 53.55" N
29° 40' 49.38" N
29° 40' 49.31" N
29° 40' 43.50" N
29° 40' 43.53" N
29° 40' 40.34" N
29° 40' 40.58" N
29° 40' 38.73" N
29° 40' 39.14" N
29° 40' 37.24" N
29° 40' 37.51" N
29° 40' 33.68" N
29° 40' 33.61" N
29° 40' 30.98" N
29° 40' 30.15" N
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
PROPOSED POLE LOCATION COORDINATES
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 18
SCALE: NOT TO SCALE
DATE: 4/12/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_BARATARIA_XY_.MXD
CZM NOTES
1. THE ENTIRE ALLIANCE SUBSTATION AREA, EXTENDING TO THE SWALES AT THE BASE OF THE PROTECTED SIDE OF
THE NEW LEVEE SHALL BE SURFACED WITH 12" OF FILL OVER A GEOTEXTILE FABRIC.
2. SWALES SHALL BE LINED WITH A GEOTEXTILE FABRIC AND COVERED WITH 6" OF #4 BALLAST IN
ACCORDANCE ENTERGY STANDARDS.
3. DRIVEWAYS SHALL MEET ALL LADOTD AND ENTERGY REQUIREMENTS, INCLUDING GRUBBING, GEOTEXTILE
FABRIC, AND PLACING 12" OF #610 GREY LIMESTONE.
4. APPROXIMATELY 9,438 CUBIC YARDS (3.54 ACRES) OF MATERIAL WILL BE DISPLACED DURING THE
EXCAVATION OF THE PROPOSED EXPANSION SURFACE. THE EXCAVATED AREA WILL BE REPLACED WITH
APPROXIMATELY 9,438 CUBIC YARDS (3.54 ACRES) OF SAND. APPROXIMATELY 6,292 CUBIC YARDS (3.54 ACRES)
OF #610 GREY LIMESTONE WILL BE PLACED ON TOP OF THE SAND. SEE SHEET 8.
5. APPROXIMATELY 2,222 CUBIC YARDS (1.38 ACRES) OF SOIL MATERIAL WILL BE USED AS FILL TO CONSTRUCT THE
PROPOSED LEVEE.
6. APPROXIMATELY 0.14 ACRES OF HERBACEOUS WETLANDS, AND APPROXIMATELY 0.70 ACRES OF
FORESTED WETLANDS WILL BE PERMANENTLY IMPACTED DUE TO CONSTRUCTION OF THE SUBSTATION EXPANSION.
APPROXIMATELY 0.24 ACRES OF FORESTED WETLANDS ARE TO BE PERMANENTLY FILLED DURING SUBSTATION EXPANSION
CONSTRUCTION AND APPROXIMATELY 0.46 ACRES WILL BE CONVERTED TO HERBACEOUS WETLANDS DUE TO CONSTRUCTION
OF THE ROW.
7. THE ENTIRE BARATARIA SUBSTATION AREA SHALL BE SURFACED WITH 12" OF #610 GREY CRUSHED LIMESTONE OVER
A GEOTEXTILE FABRIC.
8. APPROXIMATELY 7550.40 CUBIC YARDS (1.56 ACRES) OF MATERIAL WILL BE DISPLACED DURING THE
EXCAVATION OF THE PROPOSED EXPANSION SURFACE. THE EXCAVATED AREA WILL BE REPLACED WITH
APPROXIMATELY 7550.40 CUBIC YARDS (1.56 ACRES) OF SAND. APPROXIMATELY 2,516.81 CUBIC YARDS (1.56 ACRES)
OF #610 GREY LIMESTONE WILL BE PLACED ON TOP OF THE SAND. SEE SHEET 16.
9. APPROXIMATELY 1.22 ACRES OF HERBACEOUS WETLANDS, APPROXIMATELY 0.29 ACRES OF
SCRUB SHRUB WETLANDS, AND APPROXIMATELY 0.05 ACRES OF OTHER WATERS WILL BE IMPACTED DUE TO CONSTRUCTION
OF THE SUBSTATION EXPANSION. SEE SHEET 16.
FILE LOCATION: G:\ENTERGY\12900\MAPS\12900_ALLIANCE_BARATARIA_NOTES.MXD
10. FOUR ELECTRICAL POLES INSTALLED IN THE PROPOSED ALLIANCE SUBSTATION ROW WILL PERMANENTLY IMPACT APPROXIMATELY 0.0104 ACRES OF OTHER WATERS. THREE ELECTRICAL POLES INSTALLED IN THE PROPOSED BARATARIA SUBSTATION
ROW WILL PERMANENTLY IMPACT APPROXIMATELY 0.0078 ACRES OF HERBACEOUS WETLANDS. ELECTRICAL POLES WILL BE
INSTALLED ON VIBRATORY CAISON FOUNDATIONS. VIBRATORY CAISON FOUNDATION INSTALLATIONS REQUIRE NO EXCAVATION
OR FILL. SEE SHEET 9 FOR ALLIANCE CALCULATIONS AND SHEET 17 FOR BARATARIA CALCULATIONS.
11. AS-BUILT DRAWINGS SHALL BE SUBMITTED WITHIN 30 DAYS OF COMPLETION OF THIS PROJECT TO THE
LOUISIANA DEPARTMENT OF NATURAL RESOURCES, COASTAL MANAGEMENT DIVISION, P.O. BOX 44487,
BATON ROUGE, LA, 70804-4487.
12. STRUCTURES WILL BE MARKED/LIGHTED IN ACCORDANCE WITH U.S. COAST GUARD REGULATIONS.
13. IN ORDER TO ENSURE THE SAFETY OF ALL PARTIES, THE PERMITTEE SHALL CONTACT THE LOUISIANA
ONE-CALL SYSTEM (1-800-272-3020) A MINIMUM OF 48 HOURS PRIOR TO THE COMMENCEMENT OF ANY
EXCAVATION (DIGGING, DREDGING, JETTING, ETC.) OR DEMOLITION ACTIVITY.
14. NO DREDGING OR WHEELWASHING IS REQUIRED WITHIN THE PROJECT AREA.
NOTE: NO FIELD SURVEY WAS MADE FOR THIS PROJECT AND NO
ON-THE-GROUND EFFORT HAS BEEN MADE TO LOCATE AND INDICATE
ALL CABLES, PIPELINES, ETC. CROSSED BY THE PROPOSED
PROJECT. THEREFORE, MORRIS P. HEBERT, INC. IS NOT RESPONSIBLE
FOR ANY LOCATED DURING THE COURSE OF THE PROJECT.
NOTE: THIS DRAWING WAS PREPARED FOR PERMITTING PURPOSES
ONLY, AND IS NOT A PROPERTY BOUNDARY SURVEY AND AS SUCH
DOES NOT COMPLY WITH THE STANDARDS SET FORTH FOR
PROPERTY BOUNDARY SURVEYS BY THE PROFESSIONAL LAND
SURVEY LISCENSING INSTITUTE FOR THE STATE(S) ILLUSTRATED.
ENTERGY LOUISIANA, LLC
ALLIANCE AND BARATARIA SUBSTATION EXPANSIONS
JEFFERSON AND PLAQUEMINES PARISHES, LOUISIANA
CZM NOTES
SURVEYING ENGINEERING ENVIRONMENTAL SERVICES FIELD SERVICES GIS
283 CORPORATE DRIVE P.O. BOX 3106 HOUMA, LOUISIANA 70361 (985) 879-2731
10101 SOUTHWEST FREEWAY SUITE 620 HOUSTON, TEXAS 77071 (713) 219-1470
%
%
%
%
%
%
DRAWN BY: JBS
CHECKED BY:
APROVED BY:
REVISION BY:
SHEET: 19
SCALE: NOT TO SCALE
DATE: 5/1/2018
JOB NO.: 12900-00
GIS FILE: 12900_ALLIANCE_BARATARIA_NOTES.MXD